079 65246510 / 20

Ahmedabad, Gujarat (India)

triangle
About Us

Superex FR

Flame Retardant Cable - upto 1100V

Applications : Suitable for use in conduit and for fixed, protected installation.

Conductor : Many thin strands of Electrolytic Copper are fine - drawn simultaneously for uniformity of Resistance, Dimension, and Flexibility. The drawn strands are twisted in high precision machines which imparts circularity to the conductor.

Insulation : Specially formulated Lead free + Flame retardant PVC insulation is used. The FR (flame retardant) property retards the propagation of flame without compromising safety.

Insulation Conformity : IS 5831 Type A, FR

Approvals : IS 694 marked, FIA/TAC approved - CM/L 7205255

Marking : The cables are printed with generic marking “SUPEREX-FR”

Colours : Red, Yellow, Blue, Black, Green, Grey.

Packing : 90 mtrs. coils packed in protective cartons. Project coils of 180 mtrs also available.

Sizes, Dimensions and Ratings

Conductor
Area
(sq. mm)

Insulation
Thickness
(mm)

Number
Nominal Dia.
of Strands

Approx
Overall Dia.
(mm)

DC Conductor
Resistance (Π/Km)
at 20°C (Max)

Current Rating Amps.

Casing Concealed

1

0.6

14/0.3

2.8

18.1

14

13

1.5

0.7

22/0.3

3.1

12.1

18

16

2.5

0.8

36/0.3

3.7

7.41

24

20

4

0.8

56/0.3

4.1

4.95

32

26

6

0.8

84/0.3

4.8

3.30

42

35

* Conductor as per IS-8130 : 1984.

Properties

Properties

Test Method

Value

Limited Oxygen Index

IS 10810 P - 58

> 29%

Limited Temp. Index

IS 10810 P - 64

> 250°C